Overview

Essential functionality

The range of functions covers all essential functions to easily commission the inverter and control the operation behavior.
Measurements are available not only via the display but can also be accessed online when the inverter is connected to a monitoring system, e.g. the Delta SOLIVIA Monitor 2.0.

High efficiency

A reduced number of functions does not mean a compromise on efficiency. As with all Delta inverters, this inverter offers a high efficiency and a wide input voltage range.
The maximum operating temperature of 70 °C and full power without derating up to 57 °C, make the inverter the perfect choice for the use in countries with a hot climate.

Technical Data

Input (DC)
SOLIVIA 3.3 EU G3 TR
Max. recommended PV power 4000 WP
Nominal power 3630 W
Voltage range 125 ... 540 V
Full power MPP range 150 ... 450 V
Nominal current 13.3 A
Max. current 24.0 A
Stand-by power < 0.2 W
Output (AC)
SOLIVIA 3.3 EU G3 TR
Nominal power 3300 W
Voltage range 184 ... 264 V 1)
Nominal current 14.4 A
Nominal frequency 50 Hz
Frequency range 47.0 ... 52.0 Hz 1)
Power factor > 0.99 @ nominal power
Total harmonic distortion (THD) < 3 % @ nominal apparent power
General Specification
SOLIVIA 3.3 EU G3 TR
Model name SOLIVIA 3.3 EU G3 TR
Part number Delta EOE46010190
Max. efficiency 96.0 %
Efficiency EU 94.8 %
Operating temperature -25 ... +70 °C
Storage temperature -25 ... +80 °C
Humidity 0 ... 98 %
Max. operating altitude 2000 m (above sea level)
Dimensions / connections
SOLIVIA 3.3 EU G3 TR
Size (H x W x D) 410 x 410 x180 mm
Weight 21.5 kg
Cooling Convection
AC connector Wieland RST25i3S
DC connector 3 pairs of Tyco Solarlok
Communication interfaces 2 x RS485 (RJ45)
DC disconnector Integrated
Display 3 LEDs, 2-line LCD
Safety / Standards
SOLIVIA 3.3 EU G3 TR
Protection degree IP65
Safety class I
Configurable trip parameters Yes
Insulation monitoring Yes
Overload behavior Current limitation; power limitation
Anti-islanding protection / Grid regulation DIN VDE 0126-1-1; France/Islands (60 Hz); RD 661/2007; UTE C15-712-1; EN 50438; G83/1-1; VDE-AR-N 4105
EMC EN61000-6-2; EN61000-6-3; EN61000-3-2; EN61000-3-3
Safety EN60950-1; EN50178; IEC62103; IEC62109-1/ -2

1) AC voltage and frequency range are programmed according to the individual country requirements.

Downloads

  • Country:
  • Language:

Accessories